Temperature Control of a Semiconductor Process Tool
by Matt Koch, Thermo Fisher Scientific
October 1, 2007
 |
|
The SWX-100 heat exchanger was a
suitable alternative for a chiller in a heat-removal application in the
semiconductor industry.
|
|
Both a heat exchanger and two configurations of chillers
were evaluated for support of a 300 mm physical vapor deposition (PVD) tool. Which
came out on top?
While chillers, or refrigerated temperature control
equipment, have traditionally been viewed as the preferred choice for removing
heat from process equipment or for controlling temperature, heat
exchangers can represent a viable alternative, depending upon the application and
the degree of control required.
The two critical variables enabling the use of heat exchangers are a facility’s
water supply temperature and process fluid temperature stability. If these two
variables are sufficiently low, heat exchangers can provide an optimal
solution. A look at how a memory manufacturer applied the technology with
positive results can demonstrate its potential.
In general, optimal temperature control is achieved by using equipment that
offers stable, reliable performance as well as a low cost of ownership. When
tallying ownership expenses, both equipment and operating costs such as
maintenance and electricity must be considered. While chillers typically are
recommended for process cooling applications, they may not always be the
optimal equipment when both equipment and operating costs are considered.
Although both chillers and heat exchangers have recirculation
subsystems, chillers also have refrigeration subsystems, which make them
inherently more complex. In addition, refrigeration subsystems typically add
more expense on a cost-per-heat-load basis. Therefore, if raw heat removal at
moderate process fluid temperature stability is permissible, and if the process
fluid supply temperature is higher than the facility’s water supply
temperature, heat exchangers often become an attractive alternative to
chillers.
Improving Process Fluid Control
|
|
|
Table 1. Two chiller options
were evaluated to determine whether they could meet the requirements of the PVD
tool. |
|
Because
a facility’s water is prone to fluctuations in quality, temperature and
pressure, it is sometimes desirable to isolate the application from the water
supply by using a chiller or heat exchanger. This promotes better process fluid
quality, higher process fluid supply pressures for higher process fluid flow
rates, and better control of process fluid supply temperatures.
The following case is a specific example from the semiconductor manufacturing
industry. Both a heat exchanger and two configurations of chillers were
evaluated for support of a 300 mm physical vapor deposition (PVD) tool. A heat
exchanger best met the requirements of the tool, including lowest cost of
ownership.
PVD Tool Requirements. The PVD tool has identical
left and right halves. Each half has various process chambers, and each process
chamber has various components such as cathodes, stages, walls and pumps, most
of which require water cooling.
The water is supplied to these various components via two manifolds, referred
to as the cathode manifold and the module manifold. Both manifolds require a
supply pressure between 30 psi(g) and 150 psi(g), a supply temperature between
68 and 77 oF (20 and 25 oC), and a
supply resistivity of 1/100 MΩ-cm or 10 kΩ-cm. Also, the cathode and module manifolds require a flow
rate of 18.5 gal/min and 10 gal/min, respectively. The maximum supply pressure
should not be exceeded to prevent damage to the components.
Typical supply and return lines between the temperature control equipment and
the cathode and module manifolds, including fittings such as elbows and valves,
are estimated to introduce a pressure drop of up to 35 psi(d). Thus, the supply
pressure at the chiller or heat exchanger typically has to be higher than 65
psi(g) when the return pressure to the chiller or heat exchanger is 0 psi(g).
The latter typically is the case in open-loop temperature control equipment
that contains reservoirs.
Chiller Performance. Two chiller options were
considered as alternatives to the heat exchanger in order to meet the
requirements of the PVD tool: a single HX-750 chiller and two chillers, Models
HX-300 and HX-500, used in tandem. While the heat load capability of these two alternatives
was sufficient, the inability to provide pressure via one unit and the need to
provide flow rate via two units were undesirable. The matchup between chillers
and tool is shown in table 1.
|
|
|
Table 2. A heat exchanger was
evaluated to determine whether it could meet the requirements of the PVD tool.
In this application, the heat exchanger best suited the job. |
|
Heat Exchanger Performance. The
SWX-100 unit is rated for a heat load of 100 kW with a 25 gal/min facilities
flow rate and a 25 gal/min process flow rate when the temperature difference
between process supply and facilities supply is 18 oF
(10 oC). The performance can be de-rated with that
difference as long as the flow rates remain equal and both remain close to the
process flow rate of 25 gal/min. For example, at a temperature difference of
9 oF (5 oC), the heat load that can
be handled by the SWX-100 is only 50 kW. Therefore, at a
typical facilities supply temperature of 60 oF (about
15 oC), up to 50 or 100 kW can be removed from the tool
if the process supply temperature is 68 or 77 oF (20 or
25 oC), respectively. This performance does not change
substantially as the process and facility’s flow rates are increased from 25
gal/min to 28.5 gal/min to accommodate the requirements of this particular
tool. Furthermore, these figures indicate maximum
performance. A reduction from these figures is achieved automatically by
facility supply valve modulation. The CP-13 pump of the SWX-100 system can
deliver the required process flow rate of 28.5 gal/min at a process supply
pressure of about 130 psi(g). In order to establish this flow rate at the
predicted supply pressure of no more than 65 psi(g), pressure reduction is
necessary. Thus, the need for external valves becomes evident; the SWX-100 unit
has no internal flow control valves. For reference, the facilities pressure
drop within the heat exchanger at a facilities flow rate of 25 gal/min is 12.5
psi(d). The matchup between heat exchanger and tool is shown in table
2. Assuming a permissible temperature rise across the tool
of 18 oF (10 oC), the tool will be
generating 75.3 kW at most, which is likely to result in a process supply
temperature of 72.5 oF (22.5 oC).
However, given that a HX-750 unit with a heat load capacity of 24 kW was
sufficient to handle the heat load, if not the flow rate, the actual
temperature rise likely will be no greater than 5.7 oF
(3.2 oC).
Heat Exchanger in Use
The combination of the SWX-100 heat exchanger and the 300 mm
PVD tool was deployed at a major memory manufacturer on the East Coast. The
SWX-100 unit was installed so that it provided a process flow rate of up to 35
gal/min at a process supply pressure of up to 85 psi(g) to the tool. The
initial resistivity was 12 MΩ-cm,
which went down to the desired level of less than 10 kΩ-cm as time
progressed.
This application more than met the flow requirement but exceeded the
resistivity limit. If simplistic scaling of process supply pressure with the
square of process flow rate is assumed, the target process flow rate of
28.5 gal/min could be achieved at a process supply pressure of 56.4 psi(g),
falling reasonably close to the predicted number of 65 psi(g). Furthermore, the
resistivity could be reduced simply by eliminating the deionization cartridge,
thereby also eliminating a maintenance need.
The heat exchanger’s pump allowed the user to exceed the tool’s flow rate
requirement, whereas previous attempts to use chillers in this application had
consistently fallen short. Effectively, this qualified the SWX-100 unit as
support equipment on the tool. Because the tool manufacturer leaves selection
of such equipment to the end user, this is particularly significant. The memory
manufacturer was able to replace chillers with heat exchangers without further
qualification. This option has proven to be an effective alternative for the
end user’s heat removal application needs.
|