Although
an easy-to-forget component in a thermal fluid heating system, the expansion
tank is vitally important to reliable system operation.
The
expansion tank is a very important and oft-ignored component of the thermal
fluid system.
Most owners pay attention to the other components in the thermal fluid system.
They maintain the combustion system on the heater, maintain alignment and
mechanical seals on pumps, maintain instrumentation and control valves, and
inspect heat exchangers. They may even have their thermal fluid tested regularly,
but because it is a static piece of equipment, these same people often neglect
the expansion tank.
In my consulting practice, I often visit sites where there are complaints
centered on startup difficulties and fluid degradation problems. On one visit,
when I asked to take a look at the expansion tank, it took about 15 minutes to
find it! When we did find the expansion tank, it was obvious that no one had
paid attention to this piece of equipment for a long time. It was no wonder
that this facility was having problems.
Far from being a forgotten component in the system, the expansion tank is of
vital importance to the reliable operation of the system. While the expansion
tank is a static piece of equipment, it still needs to be monitored and
operated.
Purpose of the Expansion Tank
Advertisement
The
expansion tank serves four distinct and equally important roles in the thermal
fluid system:
Ensuring that the system is completely flooded.
Serving as the reservoir for the heat transfer fluid to expand into
as the fluid heats up.
Separating water and other non-condensable species from the fluid on
startup.
Controlling the environment between the heat transfer fluid and the
atmosphere.
I’ll take a closer look at each function.
Ensuring That the System Is Completely Flooded. It
is important that the thermal fluid system be completely flooded with fluid.
Any bubbles will affect the performance of the pump, can cause overheating in
the heater coil, and can negatively affect heat transfer in the heat users. To
this end, the expansion tank should be located at the highest point in the
system.
If design constraints prevent the proper location of the expansion tank, it can
be located lower, even at grade, but the tank must be pressurized with nitrogen
(or other inert gas) to provide enough pressure to force the fluid to the high
point. It should be noted that systems with low-mounted expansion tanks may not
be as easy to fill or de-gas as systems with properly located tanks.
Expansion Reservoir (Sizing the Expansion Tank).
In the part one of this series (“Choosing the Heat Transfer Fluid,” January
2007, p. 32; see Related Sites at the bottom of the page for online link to
article), I stated that choosing the heat transfer fluid is the single most
important decision made in specifying a new system. Here is one reason why:
Depending on the temperature of the system and the heat transfer fluid chosen,
the fluid can expand in volume from as little as 20 percent to more than 35
percent. The owner needs to have the following information to properly estimate
the required size of the expansion tank.
The thermal fluid to be used and its coefficient of thermal
expansion.
Minimum (startup) temperature.
Maximum (design) temperature.
Total volume of the thermal fluid system.
With this information, the total expansion of the thermal fluid, in gallons,
can be calculated. Ideally, one would want the expansion tank to be about
one-quarter full with the system ready to start up and about three-quarters
full with the system at full design temperature.
Figure
1. In this example, the expansion tank has two pipe legs and includes a valve
on the upstream leg as well as a block valve between the legs. This arrangement
allows the flow of heat transfer fluid to be diverted through the expansion
tank when desired.
Figure 1
shows a simple diagram of an expansion tank with two pipe “legs” for expansion.
Note the existence of a valve on the upstream leg and a block valve between the
two legs. This arrangement allows the flow of heat transfer fluid in the system
to be diverted through the expansion tank when desired. During startup, or if
the presence of noncondensable contamination in the fluid is suspected, fluid
is diverted to circulate through the expansion tank. Air bubbles, water (as
steam), and any low-boilers will separate from the fluid, where they can be
released from the system.
Note that the downstream leg of the expansion tank does not have an isolation
valve. It is extremely important that the fluid always have a path to travel to
the expansion tank and that no part of the system be isolated from that path
while the system is operational. The high coefficient of expansion of heat
transfer fluids can result in extremely high pressures with only a few degrees
of temperature change.
Some manufacturers offer alternate designs to the double-leg expansion tank,
and these designs work with varying degrees of success. The intent of these
alternatives is to accomplish the operational requirements outlined herein and,
in some cases, to differentiate that manufacturer’s product from others in the
marketplace. These designs will not be evaluated in this article, but they
should be evaluated by experienced personnel when decisions are being made
regarding new thermal fluid systems.
Placement of the tank is important. It should be positioned on the main
circulation loop on the suction side of the pump. In this location, it helps
ensure that the pump has flooded-suction conditions, which makes system filling
and de-gassing much more efficient.
Controlling the Environment at the Fluid-to-Atmosphere Interface.
The owner, or his outside resource, must evaluate the thermal fluid chosen to
determine what environmental controls need to be installed on the expansion
tank. The evaluation should consider the following questions regarding fluid
properties (as well as others, perhaps) to make a proper determination:
What is the vapor pressure of the fluid at operating
temperature?
What is the flashpoint of the fluid? Is that temperature lower than
the operating temperature?
Does the fluid contain any constituents that are listed under OSHA or
SARA?
Does the fluid have an odor?
What is the fluid’s intrinsic resistance to oxidation?
If the fluid has a high vapor pressure, low flashpoint, an odor, has listed
components or is prone to oxidation, the owner will be well served to place the
fluid under an inert gas blanket. In most cases, the inert gas is nitrogen,
although I have seen carbon dioxide, argon, and combustion inert gas. The inert
blanket provides the following benefits:
The pressure can be adjusted to keep fluids with high vapor
pressures from flashing.
The inert gas blanket keeps oxygen away from the fluid and reduces
the danger for fire.
If the fluid is listed under OSHA or SARA, the fluid vent can be
piped away to an appropriate collection point.
If the fluid has an odor, the gas blanket can reduce the amount of
fluid that may escape and cause an odor problem.
If the fluid has a low resistance to oxidation, the inert gas keeps
oxygen away from the fluid and extends fluid life.
Figure
2. In this simple arrangement for applying an inert gas blanket, two pressure
regulators are used to allow the expansion tank to build or lose pressure over
a predetermined range as the level in the tank goes up and down.
Figure 2
shows the simplest arrangement for applying an inert gas blanket to an
expansion tank. The supply regulator is set at the lowest pressure that will
allow the system to run effectively, but generally at least 3 to 5 psig. The
backpressure regulator is set for a higher pressure, generally about 10 psig
higher than the supply regulator. This allows the expansion tank to build or
lose pressure over a predetermined range (as the level in the tank goes up and
down with expansion) and reduces inert gas consumption.
The small bypass valve shown on the backpressure regulator in figure 2 is for
startup. This valve generally is a very small globe valve or a needle valve and
is partly opened to vent any water and low boilers present out of the system in
a controlled manner.
Figure
3. The inert gas blanket also can be controlled using a single pressure
transmitter and either dual-pressure controllers or a single “differential gap”
pressure controller with dual outputs. The small control valves have reduced
flow coefficients and admit or vent gas at the same rate as a discrete pressure
regulator.
One
problem that can occur with a dual regulator arrangement is that the
backpressure regulator can occasionally experience high temperatures if hot
fluid is in the tank and heats the inert gas to a very high temperature. One
way to address this reliability issue is to install a pressure controller and
replace the two regulators with small control valves. A single pressure
transmitter can be used and either dual-pressure controllers or a single “differential
gap” pressure controller with dual outputs can be used. The small control
valves have reduced flow coefficients (CV) and admit or
vent gas at the same rate as a discrete pressure regulator. While this
arrangement is more expensive than regulators, it is more reliable,
particularly when the ability of the control valves to “ride through” a high
temperature event is taken into account. Figure 3
shows an inert gas control loop arrangement on an expansion tank.
Table
1. The expansion tank and all of its instrumentation, accessories and
components should be matched to the system and the heat transfer fluid
properties.
It
is good practice to construct expansion tanks to a recognized code. These tanks
endure temperature cycling and often contain liquid at a temperature above its
flashpoint. For these and other reasons, it is in the owner’s interest to show
that the expansion tank was built to a generally accepted code or
standard.
In order to have traceability of the materials and procedures used to construct
the tank, I specify that expansion tanks be constructed in accordance with ASME
Section VIII, Division 1 of the pressure vessel code on projects where I have
input. This requirement results in a tank constructed with materials and weld
materials traceable to a national standard, and with welds made by a certified
welder. A tank that will never be operated above one atmosphere positive
pressure (14.7 psig) is not required to have any code stamps in most states;
however, a tank that is manufactured to ASME Section VIII can be inspected and
have a stamp applied for only a few hundred additional dollars.
It is important for the owner to determine for himself what local, state or
other codes or standards apply at the point of use of the equipment when
specifying any equipment for thermal fluid service.
Figure
4. This expansion tank schematic shows the minimum instrumentation and
appurtenances that should be used for safe, effective operation.
The
expansion tank is a component of the thermal fluid system and, as such, needs
to be operated. As a minimum, the fluid level in the expansion tank should be
recorded daily to monitor the fluid inventory. The level device can be as
simple as an armored gauge glass or as sophisticated as an electronic level
transmitter, but the fluid level should be monitored. Decreases can indicate
loss of fluid due to leaks or volatility. Increases can indicate contamination
from leaking heat exchangers, the process or other sources.
A low level switch (shown in the figures as LSLL) is installed on the tank and
is connected to the heater shutdown circuit. This safety reduces the
possibility of running the expansion tank out of fluid and allowing the heater run without fluid.
If the tank has an inert gas blanket, the pressure of the gas blanket should be
monitored. If the inert gas blanket has a discrete source such as a high
pressure gas bottle or a dewar of liquid gas, the inventory of the inert gas
should be recorded as well.
Calibration of the pressure-relief valve (PRV) should be included in the
facility’s mechanical-integrity program. The pressure-relief valve should be
removed and calibrated periodically.
In addition, a simple pressure gauge (mounted on a connection on the top of the
tank) and temperature indicator (mounted in a thermowell located low on the
tank to ensure that the liquid temperature -- rather than the gas -- is being
measured) are a good idea. In addition, more sophisticated users will install
extra instrumentation and will monitor expansion tank conditions remotely in a
control room or at a process control panel.
Figure
5. In contrast to figure 4, this expansion tank schematic shows a fully
instrumented expansion tank. While it is meant to demonstrate what a fully
instrumented tank might look like, few expansion tanks will have all of the
devices shown.
Figure 4
shows a typical expansion tank with minimum instrumentation and appurtenances.
Symbols are labeled according to ISA standards. By contrast, figure 5 shows a fully instrumented expansion
tank. (Remember that few expansion tanks have all of the devices shown.) This
figure is meant to demonstrate what a fully instrumented tank may look
like.
A short article can only give the basics of the requirements for a properly
specified expansion tank. The reader should be aware that the expansion tank
and all of its components have to be matched to the system and fluid
properties, and the expansion tank should be properly sized and specified. Once
properly specified, close attention to the expansion tank after startup will
result in a thermal fluid system that runs more reliably over time.
Sidebar Specifying a Thermal Fluid System: A 6-Part Series
Use the links at the bottom of the page to
continue reading this six-part series on specifying a thermal fluid heating
system. You've just finished:
Part 5: The
Expansion Tank
Other parts in this series
include:
Part 1: Choosing the Thermal
Fluid Part 2: Fired Thermal Fluid Heaters Part 3: Electric
Thermal Fluids Heaters Part 4: Thermal Fluid Pumps Part
6: Piping Materials, Valves and Insulation
JayHudson, P.E. jhudson@projeng.com Jay Hudson, P.E., is president of J.G. Hudson & Associates, Salisbury, N.C., a specialty engineering firm concentrating in process-related engineering services. Jay has 35 years of experience in manufacturing processes, including chemical process, polymers, synthetic fibers, coatings and food products. He has particular experience in the specification, design and operation of thermal fluid systems. He can be reached at (704) 637-1714; e-mail jhudson@projeng.com; or visit www.projeng.com.
Author’s
Note: The information and illustrations contained in this article are included for illustrative
purposes and do not constitute a design or engineering work product. When
designing a thermal fluid system or specifying components for a thermal fluid
system, the reader should employ experienced resources, either internal or
external, to insure that recognized and generally accepted good engineering
practice is followed and that local and national codes and standards are
complied with. – JH
By: hugo chayres
Posted: December 3, 2009 1:21 PM