Auxiliary Alarms on Controllers
Besides
the control output, a controller can have extra relay or logic outputs that can
be configured as high, low, deviation high, deviation low or deviation band
alarms. Note that deviation is from the working setpoint. The usual convention
is to have the relay or logic signal drop out in the alarm condition. This
usually is defined as “fail-safe” because open-circuit relay contacts and
broken wires would give a false alarm, reckoned to be preferable to an
unrevealed alarm that the opposite logic would suffer.
However, before you depend -- and act -- on the term “fail safe,” you must
thoroughly analyze the failure modes in any alarm, interlock or shutdown chain
for loss of protection. For serious overtemperature protection, remember that the
controller could fail, so do not depend on the alarm circuit in the controller
itself. You would be wise to provide an independent second opinion in the form
of a separate alarm instrument or module on its own dedicated sensor.
Rate-of-Change Alarm. There are times when you
want to alarm on a fast-moving temperature or any process variable. For
example, you may want to anticipate and defeat a large change or a thermal
reaction. In these cases, you would specify a rate-of-change alarm and set it
in units of degrees per minute.
Load-Break Alarm. With this feature, the
controller watches and times any movement of process temperature. At the same
time, it notes its command to its power output device (a contactor, for
example), and looks for a contradiction. The controller will trigger an alarm
in the following cases.
- The heater contactor is welded closed, ignores the
controller’s command to turn off and produces a rise of process temperature.
- The heater is open circuit, ignoring the controller’s command to
deliver heat, so the controller sees that the temperature is falling.
The temperature sensor is pulled away from the process heat and
showing say, room temperature, yet the controller, seeing a low unchanging
temperature, is commanding full heat. There are other ways to pick up heater problems that do not depend on the
time-out of a temperature change.
Solid-State Relay (SSR) Monitoring. Some
solid-state relays use the controller’s turn-on logic signal wires to carry
back a pulse-coded signal to the controller that represents heater current. The
controller can then pick up and alarm on two kinds of contradiction of these two
signals:
- The SSR has failed in the short-circuit mode and is passing
current in the absence of a turn-on logic signal. In this case, the alarm can
be used to kick off a backup contactor.
- The SSR has failed in the open-circuit mode or the load circuit is
broken, so it ignores the turn-on logic signal from the controller. The alarm
here would give early warning of loss of process temperature.
Latching and Non-Latching Alarms. A process can go
into alarm and out again when the process recovers. This is called a
non-latching alarm. You might wire it not just to an audible or visible
warning, but to shut off the process and bring it back when the process returns
to acceptable.
A latching alarm remains active until it is reset. Use this action if you want
it to leave the process shut down until you attend to it.