Plant and Equipment
 |
Controller alarms can be set for
high, low or rate-of-change conditions with delay and latching options. Courtesy
of Eurotherm |
|
Among the steps to take to ensure safety in your facility,
do the following:
- Make sure that your instrumentation
provides both an overview and a detailed understanding of the plant's operating
condition.
- Have access to layout and schematic drawings and descriptions of
equipment, wiring and piping, with identification of plant items. Use these to
evaluate the control and safety implications.
- Recognize that control equipment can “fail to danger.” Typically,
this means, that the failure leaves heat, flow, level, etc., uncontrolled.
Where this is a hazard, have in place a completely independent override to head
off this risk.
- Check that you have identification labels on indicators, controls,
internal cabinet wiring, terminals, piping and components. These include such
simple matters as which switch position is “off” and which way is “increase” on
a manual control.
- Put in place procedures and priority rankings to be observed when
responding to plant alarms and off-normal events.
- Have stickers on cabinets and plant equipment showing each
manufacturer's or outside supplier's service phone
numbers.
Temperature Sensor Location.
Ensure that your thermocouples or RTDs are located where they can see the
temperatures of interest to you, and that the wiring is sound. A misplaced or
pulled-out-of-place sensor, or one whose wiring is shorted, can lead to
overheating of the process.
Broken Temperature Sensor. In most processes, you
want a broken or burnt-out (open-circuit) sensor to make your controller
default to a high reading or “broken sensor” message and turn the heat off.
(This is sometimes called “upscale burnout.”) If you don't specify otherwise,
controllers normally come configured this way, being the usual safe default.
Some processes may require a broken sensor to default to full power or some
predefined percentage of full power. (This is sometimes called “downscale
burnout.”) For example, downscale burnout is used when trace-heating an outdoor
pipe or vessel that must not be allowed to cool off. In situations where
downscale burnout is required, ensure that the controller is configured this
way and that this type is not mixed with upscale burnout controllers in the
storage area. Mixing these two up at time of controller maintenance is imprudent
and potentially dangerous.
Reversed Thermocouple. Often, thermocouple wires
are crossed when a process is being rewired or commissioned. This would
normally send the controller indication downscale and call for full heat,
perhaps damaging your equipment or making scrap product.
Consider using controllers that can recognize this as an unrealistically low
temperature and default either to power off, or to the level of power that you
specify.
Replacing Thermocouples. Some plants have a
mixture of different sensors, and it is easy to take, say, a Type R
thermocouple off the spares shelf and install it where a Type K came out. This
would make the controller drive the temperature up to some three or four times
the set value. So, identify and label spare thermocouples and controllers by
thermocouple type.
Auxiliary Alarms on Controllers. Besides the
control output, a controller can have extra relay or logic outputs that can be
configured as high, low, deviation high, deviation low or deviation band
alarms. Note that deviation is from the working setpoint. The usual convention
is to have the relay or logic signal drop out in the alarm condition. This
usually is defined as “fail-safe” because open-circuit relay contacts and
broken wires would give a false alarm, reckoned to be preferable to an
unrevealed alarm that the opposite logic would suffer.
However, before you depend — and act — on the term “fail safe,” you must
thoroughly analyze the failure modes in any alarm, interlock or shutdown chain
for loss of protection. For serious overtemperature protection, remember that
the controller could fail, so do not depend on the alarm circuit in the
controller itself. You would be wise to provide an independent second opinion
in the form of a separate alarm instrument or module on its own dedicated
sensor.
More on hazards next month.