Effectively choosing among the range of alarm types allows engineers to achieve better control over process heating applications.
Alarm Modes and Types
|
|
| Today's instruments have the ability to combine alarms using such logic operations as OR, XOR, AND and LATCH. |
|
The mode of an alarm defines how it is detected and executed. Choosing an alarm mode lets the process engineer select the best alarm response for the process conditions. Depending on the sophistication of the instrument, several alarm modes are available.
Standard Nonlatched Alarms. Set when the measured value moves from the safe zone and crosses the threshold defined by the alarm setpoint, standard nonlatched alarms will reset when the measured value moves back into the safe zone, crossing the reset threshold as defined by the setpoint less the hysteresis.
Latched Alarms. There are two types of latched alarms. Each will remain set in the alarm state, even if the measured value returns to the safe zone, until an operator executes an acknowledgement. A manually latched alarm can only be acknowledged after the alarm condition is removed. For example, a latching high-limit alarm would be used for system shutdown when the process exceeds safe operating temperatures.
An auto-latched alarm can be acknowledged at any time during the alarm condition. The alarm unit will accept the acknowledgment and clear the alarm when the unit is back in a safe state.
Blocking or Masking Alarms. Typically used on low alarms, blocking or masking alarms are only active after the startup phase following the first time the measured value achieves the safe state. The alarm is blocked during the initial start to allow the machine to achieve initial run conditions and will only indicate the next time it is active.
Alarm Delay or Alarm Inhibit. These two alarm modes commonly are used. Alarm delay imposes a short time delay before the triggering of an alarm. This is done to avoid nuisance alarms when spurious process noise is present. Alarm inhibit suspends an alarm action for the duration of an external or internal inhibit signal. Alarms may be inhibited during maintenance activity or during operations not involving the alarmed equipment.
Combined Alarm Mode. Combined alarm modes allow the collection of multiple instrument alarms by a logical function within the instrument (most commonly the OR function). The resultant output is attached to a single relay output. This enables alarm strategies that can eliminate multiple external alarm-collection hardware. Today's instruments have the ability to combine alarms using such logic operations as OR, XOR, AND and LATCH.
Alarm Output Relay. Output relay for an alarm may be configured to energize or de-energize when the alarm is set. They often present both the NO and the NC contacts for external connection. Combining these features provides flexibility in selecting an alarm strategy to match the plant requirements. An alarm that is configured such that its coil is energized and its NO contacts are closed when the alarm is OFF is considered failsafe because the external circuit through the alarm relay is complete only if there is no alarm and the instrument is working properly.
The level of functionality, programmability and alarming choices in today's instruments provide users with the ability to create a local alarm strategy that can best achieve the competitive goals of operating safely, reducing costs, minimizing downtime and improving quality.