Figure 1. Use this test setup to measure your heat load. The thermocouples and flowmeter can be used to measure the fluid temperature change and flow rate of the cooling fluid when your system is at peak load operation.
A quick and dirty method of estimating heat load is to assume that all of the electrical energy entering a process is converted to heat. From the First Law of Thermodynamics, you know that the amount of energy exiting a system can never be greater than the amount of energy entering a system. The heat load can be conservatively estimated to be equal to the amount of electricity consumed if electricity is the only form of energy entering a system.
To determine the heat load more accurately, use the following equation
Q = m x Cp x ΔT
where
Q is the heat load (BTU/hr).
m is the mass flow rate (lb/hr).
Cpis the specific heat (BTU/lb °F).
ΔT is the change in temperature (°F).
In order to determine Q using the above equation, it is necessary to obtain the values m and ΔT experimentally. To measure these values, you will need a Type T thermocouple and a turbine flowmeter (table 1).
The thermocouples and flowmeter can be used to measure the fluid temperature change and flow rate of the cooling fluid when your system is at peak load operation (figure 1). Using the fluid’s specific heat and the equation, the heat load can be computed.
The accuracy of the thermocouples and flowmeter is particularly important, as a small decrease in accuracy can cause a significant error percentage. For example, if the temperature rise is 10°F (5.5°C) and the thermocouples are accurate to ±0.5°F (±0.27°C), the temperature rise measurement could be off by as much as 1°F (0.55°C), or 10 percent. This dictates that the entire heat load calculation cannot be more accurate than the same ±10 percent. If the temperature rise is less than 10°F, then the ±0.5°F becomes an even higher error percentage. (When the temperature error is given in °F or °C, the error percentage can be calculated by multiplying the thermocouple accuracy by two, then dividing by the change in temperature, and multiplying by one hundred.)

Table 1. In order to determine heat load (Q) using the equation, it is necessary to obtain the mass flow rate and temperature differential experimentally.
(87-77) - (69-68), or 9°F
(30.5-25.0) - (20.5-20.0), or 5.0°C
If a flowmeter is not available, a graduated container and a timer can be used to determine the fluid flow rate by measuring the amount of fluid that has passed through the system and dividing by the amount of time that has elapsed. A constant flow rate is essential when measuring the flow in this manner. The density of the fluid should be used to convert the volumetric flow rate to mass flow rate.
These methods of determining heat load are generic to any liquid cooling application and can be used when sizing a chiller, cold plate or heat exchanger.